English
Leave Your Message
655ddc4ece25e726951rx

Lead-acid Battery Monitoring Solution

Overview

Acrel ABAT100 series battery online monitoring system can provide battery operation information such as voltage, internal resistance and internal temperature, including SOC and SOH, and can provide early warning and battery equalization for failed batteries to guarantee battery pack backup time and extend battery pack life.
The system has monitoring functions, and is easy to install, maintain and access.
The system mainly consists of ABAT100-S single battery monitoring module, ABAT100-C group battery monitoring module, ABAT100-HS collector module and touch screen, etc.
The alarm and real-time data can be queried and parameters can be set through the touch screen, and the monitoring platform can be selected to realize networked centralized management.

Applicaiton Scenarios

 Data Center UPS
 Tower Base Station
 Petroleum&Petrochemicals
 Rail Traffic

Structure

17121248387121pw
1712124845969toc

Rated Products

Product Name

Picture

Function

ABAT100-HS Data collector

图片1w30 

1.It is used to manage and collect the data of the front-end distributed single battery monitoring module, and perform data processing, analysis, alarm generation, saving and uploading;

2.One collector can manage 1 group, 120 batteries;

3.Automatic data analysis and processing can estimate the remaining capacity of the battery;

4.Support MODBUS protocol and can be connected to third-party monitoring system.

 

ABAT100-S Single battery monitoring module

图片2uv5 

1.Online monitoring 24 hours a day to find batteries with degraded performance at any time;

2.Divided into three detection ranges of 2V, 6V and 12V, meeting the requirements of most batteries;

3.Each module monitors a battery, monitors voltage, internal resistance and negative electrode temperature;

4.The installation is simple, the positive and negative poles are connected to a wire, and it can be installed without special training..

 

ABAT100-C single group battery monitoring module

图片3v9m 

1.Online monitoring of charging and discharging current and ambient temperature 24 hours a day

2.With photoelectric isolation, support MODBUS protocol, easy access to third-party monitoring system

3.High performance, reliable and stable

 

C module matching Hall current sensor

图片46b2 

 

ATP Touch Screen

图片57xl 

1.Real-time data, alarm information, event query and statistics

2.Diversified graphical displays such as curve charts and column charts

3.RS485 serial port / RJ45 network port / USB interface

4.24VDC Power Supply

5.Embedded installation

6.7/10 inch industrial grade touch screen optional

Selection Example

One set of backup batteries for each 500KVA UPS host consists of four sets of 200Ah/480V (each set consists of 40 200Ah/12V batteries connected in series).

Configure the following scheme according to the project information Battery monitoring configuration scheme under each UPS host:

Serial

Name

Type

Quantity

Function Description

1

Single battery monitoring module

ABAT100-S-12

4*40

Single battery voltage, temperature and internal resistance monitoring - 12V

2

Single battery monitoring module

ABAT100-C

4

Current and temperature monitoring of a single battery pack

3

Single battery data acquisition module

ABAT100-HS

4

Collect and summarize the data of S and C modules in a single battery pack, and the HS module can access up to 120 S modules

4

Hall sensor

AHKC-EKB 500A/5V

4

Charge and discharge current monitoring of a single battery pack

5

7 inches touch screen

ATP007KT

1

For local data display, up to 6 HS modules can be connected

6

Switching power supply

KDYA-DG1502-12K

1

Used for HS acquisition module, touch screen power supply

7

Smart gateway

AWT200-1E2S
ANET-2E4SM

1

Collect data and transmit it to the system platform for display

Platform Interface

微信截图_20240514130239cqr
微信截图_20240514130147fp5

Platform Demo Adress :https://iot.acrel-eem.com/

Admin:Acrel   Password:123456

 Project