010203
DTSD1352-4S Base Station Multi-circuit AC Power Meter
OVERVIEW
DTSD1352-4S series din-rail multi-loop power instrument is mainly used for the measurement of full electrical parameters of multiple loops, and can access the current input of up to 4 three-phase loops or 12 single-phase loops at the same time. It can measure the voltage and current, power, power factor, phase Angle, unbalance degree, harmonics and other parameters of the mains, oil engine, air conditioner and socket.
MAIN PARAMETERS
Auxiliary Power | AC/DC 85~265V; power consumption<10VA; | ||
Input Signal | Frequency | 45~65Hz; | |
Voltage | Rated value: AC 3x220V/380V; | ||
Overload: 1.2 times rated value (continuous);, 2 times rated value/1 second; | |||
Power Cconsumption: ≤0.5VA (each channel) i | |||
Current | Rated value: Secondary input rated current: 50mA | ||
Overload: 1.2 times rated value (continuous); 10 times rated value/1 second; | |||
power consumption:≤0.5VA (each channel) i | |||
Measurement Accuracy | Frequency: 0.05Hz, voltage and current: 0.5 class, active energy: 1 class, reactive energy: 2 class,.2nd to 31st harmonic accuracy: +1%; | ||
Function | Pulse output | Output method: optocoupler pulse with open collector,the pulse constant defaults to 400imp/kWh (and active open input can only be either-or); | |
communication | RS485 interface, Modbus-RTU protocol; baud rate 1200~38400; | ||
Switch | Input | 2-way or 4-way passive dry contact iput, built-in power supply; 2-way active wet node input (AC220V), identify the oil generator and mains access (and pulse output can only be either-or); |
|
Output | Output method: relay normally open contact output; Contat rating; AC 250V/3A DC 30V/3A; |
FUNCTIONS
GFSK Wireless Communication
● Wireless Frequency: 470MHz
● Communication Distance: 150m in open area
Wide Range of Temperature Measuring
● Extreme Range of Measuring: -50℃~+125℃ (General Type)
● Extreme Range of Measuring: -50℃~+125℃ (IP68 Type)
● Recommended Operation Temperature: ≤85℃ (Battery power supply)
● Recommended Operation Temperature: ≤105℃ (CT sensing power supply)
A Installation Methods
● Fixed by alloy chips
CT Sensing Power Supply
● Lifespan: ≥5 years (battery); ≥10 years (CT sensing)
DISPLAY
COMMON APPLICAITON
APPLICAITON SCENARIOS
COMMON APPLICATION STRUCTURE
CLOUD+LOCAL SOLUTION
Local Only Solution
INSTALLATION INSTRUCTION VIDEO
Manual of AMC Series AC Multi-function Panel Energy Meter
CE Certificates of AMC Series AC Multi-function Panel Energy Meter
Quotation of AMC Series AC Multi-function Panel Energy Meter